31005 VTC-OA - 1
31005 VTC-OA - 2
31005 VTC-OA - 3

31005 VTC-OA

DC voltage detector - Optical & Acoustic

645210 645211


 

Voltage range:
500 V < Vt < 5000 V
Usage frequency:
DIRECT current
Operating temperature:
-25°C to 55°C
Humidity Range:
20 to 96 %
Indication of alert status:
Through high luminosity green LED.
There is no voltage or it is below the established detection threshold.
Indication of voltage presence:
Optical/Acoustic indication through high luminosity red LED and high pressure acoustic buzzer*.
Battery:
9 V battery, type 6LR61
Low battery indication by flashing green LED, when battery level is critical green led is off.
Earthing cable:
Extra flexible cable with silicon sheath and 6 m long (possibility of other lengths at customer’s request).
Isulating pole:
With universal head
Self-checking:
Full self-checking system with automatic disconnection after two minutes WITHOUT DETECTION.
Automatic start-up:
Automatic start-up system using detection of voltage (approx. 400V dc).
Electrode:
Possibility of exchanging electrode
Threshold voltage:
Threshold 1 - From  350 to 490 V: Red led
Threshold 2 - From 900 to 1100 V: Red and orange led

Ref. 346
Share it:

Specifications